HGM1790N Genset Controller User Manual Page 18 of 31
No.
Parameter
Range
Default
Value
Description
sensor which connected to the
temperature sensor input port. If the set
value is 140, high temperature signal will
not be sent (this only concerns
temperature sensor, not high
temperature signal via config. input
port).
P23
Low Oil
Pressure
(0-400)kPa
103
When the external pressure sensor value
falls below this threshold, low oil
pressure delay begins. Detection begins
after safely on delay. If the set value is 0,
low oil pressure signal is not sent (this
only concerns pressure sensor and does
not concern low oil pressure warning
signal via configurable input port)
P24
Low Liquid
Level
(0-100)%
10
When the liquid level of the external
sensor falls below this value and stays
so for 10s, low liquid level signal is sent
and warning without shutdown is
initiated.
P25
Battery Over
Volts
(12-40)V
33.0
When battery voltage exceeds this value
and stays so for 20s, Battery Over Volts
signal is sent and warning without
shutdown is initiated.
P26
Battery Under
Volts
(4-30)V
8.0
When battery voltage falls below this
value and stays so for 20s, Battery Under
Volts signal is sent and warning without
shutdown is initiated.
P27
CT Ratio
(5-6000)/5
500
Current transformer ratio default as
500:5.
P28
Full-load Current
(5-1900)A
500
It is the rated current of generator, which
is apply for calculating over current with
load.
P29
Over Current
Percentage
(50-130)
120
Over current delay starts when current
with load is greater than value of
full-load current multiply over current
percentage.
P30
Over Current
Delay
(0-3600)s
60
When current with load exceeds preset
value and stays so over delay time, over