HGM6100LT Series Genset Controller User Manual                                                                  Page 41 of 50 
13    CONNECTIONS OF CONTROLLER WITH J1939 ENGINE 
13.1  CUMMINS ISB/ISBE 
Table 13 – Connector B 
Set  programmable  output  1  as  “Fuel 
Output”. 
Connect with starter coil directly. 
Expand  30A  relay,  battery 
voltage of 01, 07, 12, 13 is 
supplied by relay.   
ECU power;   
Set  programmable  output  2  as  “ECU 
power”. 
Table 14 – 9 Pins Connector 
CAN  communication  shielding  line 
(connect to ECU terminal only). 
Using impedance 120Ω connecting line. 
Using impedance 120Ω connecting line. 
Engine type: Cummins ISB. 
13.2  CUMMINS QSL9 
Suitable for CM850 engine control module. 
Table 15 – 50 Pins Connector 
Set  programmable  output  1  as  “Fuel 
Output”. 
Connect to starter coil directly. 
Table 16 – 9 Pins Connector 
CAN  communication  shielding  line 
(connect to ECU terminal only). 
Using impedance 120Ω connecting line. 
Using impedance 120Ω connecting line. 
Engine type: Cummins-CM850.