HGM6100LT Series Genset Controller User Manual Page 44 of 50
13.7 CUMMINS QSZ13
Table 24 Engine OEM Connector
Terminals of controller
OEM connector of engine
Remark
Programmable output 1
45
Starting relay output
-
Connect to starter coil directly.
Programmable output 2
16&41
Setting to idle speed control, normally
open output. Making 16 connect to 41
during high-speed running of controller via
external expansion relay.
Programmable output 3
19&41
Setting to pulse raise speed control,
normally open output. Making 19 connect
with 41 for 0.1s during high-speed
warming of controller via external
expansion relay.
CAN_SCR
-
CAN communication shielding line.
CAN(H)
1
Using impedance 120Ω connecting line.
CAN(L)
21
Using impedance 120Ω connecting line.
Engine type: Common J1939.
13.8 DETROIT DIESEL DDEC III / IV
Table 25 Engine CAN Port
Terminals of controller
CAN port of engine
Remark
Programmable output 1
Expand 30A relay, battery
voltage is supplied by
relay.
Set programmable output 1 as “Fuel
Output”.
Starting relay output
-
Connect to starter coil directly.
CAN_SCR
-
CAN communication shielding line.
CAN(H)
CAN(H)
Using impedance 120Ω connecting line.
CAN(L)
CAN(L)
Using impedance 120Ω connecting line.
Engine type: common J1939.