HGM6100LT Series Genset Controller User Manual                                                                  Page 39 of 50 
12    INSTALLATION 
12.1    FIXING CLIPS 
—  The module is held into the panel fascia using the supplied fixing clips.     
—  Withdraw the fixing clip screw (turn anticlockwise) until it reaches proper position. 
—  Pull the fixing clip backwards (towards the back of the module) ensuring four clips are inside their 
allotted slots.   
—  Turn the fixing clip screws clockwise until they make contact with the panel.   
NOTE: Care should be taken not to over tighten the screws of fixing clips. 
12.2    OVERALL DIMENSION AND PANEL CUTOUT 
 
Fig.9 – Case and Overall Dimensions 
HGM6100LT  series controller  can be  applicable to  (8~35) VDC  battery voltage. Battery negative 
must be reliably connected to engine shell. The connection between controller power (B+ and B-) and 
battery (B+ and B-) should not be less than 2.5mm
2
. If a floating charger is fitted, please connect output 
line of the charger with battery directly, and then connect battery positive and negative to power input 
of controller separately, in case that charger will interfere with the normal running of controller.     
1)  Speed Sensor Input 
Speed sensor is installed in the engine for testing flywheel teeth. The connection with controller 
uses  2-core screen,  shield  layer  should  be connected  to  terminal  16  of  controller  and  the  other end 
vacant. The  other two  signal  lines  are respectively connected to  terminal  15 and terminal  16. At full 
speed,  output  voltage  range  is  (1~24)  VAC  (RMS),  12VAC  is  recommended  (rated  speed).  During 
installing, make the speed sensor contact the flywheel firstly, then pour out 1/3 laps, finally lock nut on 
the sensor. 
2)  Output and Expansion Relay 
All  the  outputs  of  controller  are  relay  output.  If  need  to  expand  relay,  please  add  freewheeling 
diode in both ends of relay coil (when expansion relay coil links DC), or add RC loop (when expansion 
relay coil links AC), in case interfering controller or other equipment. 
3)  AC Input 
HGM6100LT  series  controller  must  externally  connect  to  current  transformer;  CT  secondary 
current  must  be  5A.  Besides,  the  phase  of  CT  and  input  voltage  must  be  correct,  or  the  sampling 
current and active power may be incorrect.