EasyManua.ls Logo

SMC Networks EtherCAT EX260-VEC1 - Troubleshooting Tables

SMC Networks EtherCAT EX260-VEC1
33 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-31-
No.DOC1048575-1
10.2. Troubleshooting tables
Table 10-1. Troubleshooting "PWR LED is OFF or flashing"
State
Probable causes
Checking methods and measures
PWR LED is OFF.
Incorrect wiring.
Check the power cable wiring.
Check the wiring and pin numbers, refer to Section 2.2.
Power supply for logic/input
(PWR) is not present or is very
low voltage.
Check the power supply.
Check the supplied voltage for PWR.
PWR LED is
flashing. (0.5Hz)
Power supply for logic/input
(PWR) is low.
(< approx. 18 VDC)
Check the supplied voltage for PWR. Supply the voltage
considering the voltage drop on the wiring.
Table 10-2. Troubleshooting "PWR(V) LED is OFF"
State
Probable causes
Checking methods and measures
PWR(V) LED is
OFF.
Incorrect wiring.
Check the power cable wiring.
Check the wiring and pin numbers, refer to Section 2.2.
Power supply for output
(PWR(V)) is not present or is very
low voltage.
Check the power supply.
Check the supplied voltage for PWR(V). Supply the
voltage considering the voltage drop on the wiring.
Table 10-3. Troubleshooting "L/A LEDs are OFF, ERR LED is double flashing"
State
Probable causes
Checking methods and measures
L/A1 LED and
L/A2 LED are
both OFF.
Incorrect wiring.
Check the communication cable wiring.
Check the wiring and pin numbers, refer to Section 2.1.
The SI Unit is not connected to a
valid network.
Check the state of the EtherCAT
®
controller connected
to the SI Unit.
ERR LED is
double flashing.
The communication connection
disconnected.
Check the communication cable connection.
Table 10-4. Troubleshooting "RUN LED does not ON, ERR LED is blinking"
State
Probable causes
Checking methods and measures
RUN LED does
not ON.
The SI Unit is connected to some
kind of network, but the following
problems are occurring.
---
No communication with the
EtherCAT
®
controller.
Check the communication cable wiring.
Communicate to EtherCAT
®
controller.
There is a problem with the
EtherCAT
®
controller.
Check the EtherCAT
®
controller state.
ERR LED is
blinking. (2.5 Hz)
The number of connected
vacuum manifold does not match
with respect to slot setting.
Refer to Section 3.2 and set the slot settings to match
the number of the vacuum manifold connected.

Related product manuals