Chapter 3 Transporting and Installation
3.3 Procedure for Installation HRZ Series
3-8
3.3.4 Wiring installation
Power cable
The power cables are to be prepared under your responsibility, referring to the
following table.
Table 3-1 Power Cable and Main Breaker (This System)
Item
HRZ001-H
HRZ001-H1
HRZ002-H
HRZ002-H1
HRZ001-L
HRZ001-L1
HRZ001-L2
HRZ002-L
HRZ002-L1
HRZ002-L2
HRZ004-L
HRZ004-L1
HRZ004-L2
HRZ008-L2
HRZ004-H
HRZ004-H1
HRZ008-H
HRZ008-H1
HRZ002-W
HRZ002-W1
HRZ008-W
HRZ008-W1
HRZ008-L
HRZ008-L1
HRZ010-WS
HRZ010-W1S
HRZ010-W2S
Power cable
Size (recommended)
10AWG4-conductor
10AWG4-conductor
4AWG4-conductor
10AWG4-conductor
Crimp contact
(recommended)
Breaker
R5.5-5
R5.5-5
R22-8
R5.5-8
Earth bar
R5.5-8
R5.5-8
R22-8
R5.5-8
Torque
(recommended)
Breaker
2.5N•m (1.84 ft-lbf)
2.5N•m (1.84 ft-lbf)
6N•m (4.43 ft-lbf)
6N•m (4.43 ft-lbf)
Earth bar
12.5N•m (9.22 ft-lbf)
12.5N•m (9.22 ft-lbf)
12.5N•m (9.22 ft-lbf)
12.5N•m (9.22 ft-lbf)
Main breaker (This System)
20A
30A
60A
30A
Communication connector
The communication connectors are to be prepared under your responsibility,
referring to the following table.
Table 3-2 Communication Connector
Connector
Type (for your system)
Contact signal (P1 connector)
D-Sub 25-pin (male)
Serial RS-485 (P2 connector)
D-Sub 9-pin (male)
Only designated personnel are allowed to install wiring.
Be sure to turn OFF the power prior to wiring to assure safety.
Do not do any wiring when the system is energized.
The system wiring requires not only a thorough connection with the
designated cable but also securing to prevent loose connection. Poor
connection and securing may cause electric shock, heat sports, fire or
communication errors.
Be sure to supply the power to this system according to specifications.
Supply pure AC power. Potential malfunction may occur if a rectified AC
with voltage rise (dv/dt)
at zero crossing exceeds 40V /200µ sec.
Always establish a connection to a ground for safety.
Be sure that no ground connection is made to
a water pipe, gas pipe and lighting rod.
V
dV
dt
dt
= Voltage ratio
on zero-cross point
dV
t
Voltage rise %
Time
Voltage