No.IP8S-OM00009
30
Parameter Code Detail
(000) Actuator type
(200) Operation direction
setting
Displays linear (Lin)”. This parameter is fixed when shipped, and
cannot be modified.
“Direct
*3
(dir)” or “Reverse
*4
(rvS)” can be selected. The default
when shipped is “direct (dir)”.
When the operation direction is modified, it is reflected on each
item in accordance with Table 10. Suppose 30mm for actuator full
stroke as an example.
0%
100%
0%
100%
200=dir
200=rvS
0%
100%
Stroke
Input current
Fig. 23
3: Direct direction means an actuator’s operation direction which is
determined by air output from “OUT 1” port on the positioners body.
4: Reverse direction means an actuator’s operation direction which is
determined by air output from “OUT 2” port on the positioners body.
Table 10
Operation
direction
Input
current
Input
value
(S value)
Position
value
(P value)
Actuator stroke
Analog
output
(mADC)
()
()
(mm)
(mADC)
Direct
(dir)
4-20
0-100
0-100
0-30
4-20
Reverse
(rvS)
4-20
0-100
100-0
30-0
20-4

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks IP8001 Series and is the answer not in the manual?

SMC Networks IP8001 Series Specifications

General IconGeneral
BrandSMC Networks
ModelIP8001 Series
CategoryValve Positioners
LanguageEnglish

Related product manuals