Error No.
Error
Possible cause
Countermeasure
0003
Failed adjustment of
balance current
The balance current has not been
adjusted to be good (Good), but
the positioner has been set after
STEP3 to STEP5.
-Adjust the balance adjusting screw
to correct the balance current (See
Fig. 18).
0004
Hunting does not subside.
-The size of actuator is small.
-Inside of the piping is choked (with
something such as a speed
controller).
-Stop hunting with the PID constant
setting (parameter code: 800) .
See Improved Controllability”.
0005
Impossible to check the
balance current
Simple balance adjustment
(parameter code: C20 has not
been performed.
-Recalibrate the positioner
(parameter code: 30) after
performing a simple balance
adjustment (parameter code: C20).
-If the set value of the dead band
(parameter code: 600) is
changed, return the set value to 0.
0006
Input current adjustment error
(4mA DC)
-Input current deviates widely from
4mA DC.
-Check that the Input current
is 4mA DC.
0007
Input current adjustment error
(20mA DC)
-Input current deviates widely from
20mA DC.
-Ensure that the input current
is 20mA DC.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks IP8001 Series and is the answer not in the manual?

SMC Networks IP8001 Series Specifications

General IconGeneral
BrandSMC Networks
ModelIP8001 Series
CategoryValve Positioners
LanguageEnglish

Related product manuals