4 How to use
-100-
No.PS※※-OMW0009-A
Product individual parameters (continued)
Index
Sub
index
Access
1
Items
Data
type
2
Initial value
Data
storage
3
Set value
Remarks
dec
hex
1230
0X04CE
1
R/W
SUP port
pressure (OUT1)
Output mode
U8
0
Y
0: HYS
1: Wind
Setting of OUT1 output mode
2
R/W
Output type
U8
0
Y
0: Normal output
1: Reverse
output
Setting of OUT1 output normal and
reserved output
1240
0X04D8
1
R/W
HYS mode set value
S16
1000
Y
-200 ~ 2200
Setting of OUT1 output set value
2
R/W
HYS mode hysteresis
S16
200
Y
0 ~ 2400
Setting of OUT1 hysteresis
3
R/W
Wind mode lower
limit set value
S16
1000
Y
-200 ~ 2200
Setting of OUT1 output set value
(lower limit of window comparator)
4
R/W
Wind mode upper
limit set value
S16
2000
Y
-200 ~ 2200
Setting of OUT1 output set value
(upper limit of window comparator)
5
R/W
Wind mode hysteresis
S16
200
Y
0 ~ 1200
Setting of OUT1 hysteresis
(window comparator hysteresis)
6
R/W
ON delay time
U16
0
Y
0 ~ 6000
Setting of OUT1 delay time at ON
0.01 s increment (0 to 60 s)
7
R/W
OFF delay time
U16
0
Y
0 ~ 6000
Setting of OUT1 delay time at OFF
0.01 s increment (0 to 60 s)
1430
0X0596
1
R/W
SUP port
pressure
(OUT2)
Output mode
U8
0
Y
0: HYS
1: Wind
Setting of OUT2 output mode
2
R/W
Output type
U8
0
Y
0: Normal output
1: Reverse
output
Setting of OUT2 output normal and
reversed output
1440
0X05A0
1
R/W
HYS mode set value
S16
1000
Y
-200 ~ 2200
Setting of OUT2 output set value
2
R/W
HYS mode hysteresis
S16
200
Y
0 ~ 2400
Setting of OUT2 hysteresis
3
R/W
Wind mode lower
limit set value
S16
1000
Y
-200 ~ 2200
Setting of OUT2 output set value
(lower limit of window comparator)
4
R/W
Wind mode upper
limit set value
S16
2000
Y
-200 ~ 2200
Setting of OUT2 output set value
(upper limit of window comparator)
5
R/W
Wind mode hysteresis
S16
200
Y
0 ~ 1200
Setting of OUT2 hysteresis
(window comparator hysteresis)
6
R/W
Delay time ON
U16
0
Y
0 ~ 6000
Setting of OUT1 delay time at ON
0.01 s increment (0 to 60 s)
7
R/W
Delay time OFF
U16
0
Y
0 ~ 6000
Setting of OUT1 delay time at OFF
0.01 s increment (0 to 60 s)