EasyManua.ls Logo

socomec NETYS RT 5000 - Page 73

socomec NETYS RT 5000
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NETYS RT 5 - 7 - 9 - 11 kVA - 551570A - SOCOMEC
73
EN
NRT3-OP-PMB
TO UPS PARALLELTO UPS PARALLEL
TO UPS-1 OUTPUT
BYPASS MODE
UPS MODE
UPS-2UPS-1
OUTPUT BREAKERBYPASS BREAKER
WARNING:
ONLY AUTHORIZED SERVICE PERSONNEL
CAN REMOVE THIS COVER PLATE.
REMOVING THIS COVER PLATE WILL CAUSE
THE INVERTER TO SHUTDOWN. SEE THE
USERS MANUAL FOR INSTRUCTIONS.
1
4
5
2
6 7
9
10 10
3
8
TO UPS-1 INPUT
TO UPS-2 OUTPUT TO UPS-2 INPUT
NOTE :
Remove the terminal
cover plate and you will
see the wiring terminal
blocks.
N(L2)
OUTPUT
AC I NPUT
N(L2) L(L1) L(L1)
N L
N L
N L
N L
INPUTOUTPUT
No.
Item (Printed Words on
the Front Panel)
Connection
1
AC Input Connects to the main AC utility.
2
Output Connects to the critical loads.
3
Bypass Breaker
No connection is needed. After you remove the two
screws shown in
Figure 15
to remove the cover
plate, the PMB’s detector will automatically activate
and send a message to the UPS to ask it to transfer
into bypass mode.
4
UPS-1 Output Breaker
No connection is needed. The function is to prevent the
output terminals from damage caused by overload.
5
UPS-2 Output Breaker
No connection is needed. The function is to prevent the
output terminals from damage caused by overload.
6
To UPS-2 Output (L/ N/ )
Connects to the UPS2’s UPS Output terminals (L/ N/ )
7
To UPS-2 Input (L/ N/ )
Connects to the UPS2’s AC Input terminals (L/ N/ )
8
To UPS-1 Input (L/ N/ )
Connects to the UPS1’s AC Input terminals (L/ N/ )
9
To UPS-1 Output (L/ N/ )
Connects to the UPS1’s UPS OUTPUT terminals (L/ N/ )
10
To UPS Parallel Connects to the UPS’s parallel port.

Related product manuals