NETYS RT Hot Swap 7 - 11 kVA - 551574B - SOCOMEC
72
EN
Error
Code
Alarm
Message
Possible
Cause
Solution
0X6100
PFC Over Heat
Shutdown
1. The vents are
blocked.
2. The UPS has an
internal fault.
1. Check whether the
vents are blocked.
2. Contact service
personnel.
0X1003
Battery
Disconnected
1. The UPS is not
properly connected
to the external
battery pack(s).
2. The battery/
batteries is (are)
damaged.
1. Check whether
the UPS is properly
connected to the
external battery
pack(s).
2. Contact service
personnel.
If all possible causes are eliminated but the alarm still appears, please
contact your local dealer or customer service.
4. Error code on display and event list.
Error Code Alarm Message
0x0100 Mains Input Volt Out Range
0x0120 Mains Input Freq Out Range
0x0121 Input relay short
0x0122 Input Fuse Open
0x0277 Bypass relay Fault
0x02B0 Bypass Over Current
0x1001 Battery End Of Discharge
0x1002 Battery Over Charged
0x1003 Battery Disconnected
0x1004 Battery Life time Expired
0x1005 Battery Reversed
0x1012 Battery Test Fail
0x1013 Battery Test In Progress
0x1101 Output Overload Shutdown
0x1109 Output Short Circuit
0x1200 INV Volt Abnormal