13. TECHNICAL SPECIFICATIONS
Model RT-7 RT-11
Power Rating 7 kVA/6kW 11kVA/10kW
Waveform Pure Sinewave
Input
Nominal Voltage 200*
1
/208*
1
/220/230/240 Vac
Voltage Range
175 ~ 280Vac (100% load);
100 ~ 174Vac (50% ~ 100% load)
Frequency 50/60 Hz ± 10 Hz
Power Factor 0.99 (full load)
iTHD < 3% (linear load)
Connection Terminal
Electrical input supply
system
TT, TN
Output
Voltage 200*
1
/208*
1
/220/230/240 Vac
Voltage Regulation
± 1% (linear load)
Frequency 50/60 Hz ± 0.05 Hz
vTHD <2% (linear load) <3% (linear load)
Overload
Capacity
< 105%: continuous; 105% ~ 125%: 2 minutes;
125% ~ 150%: 30 seconds; >150%, <500 ms
Crest Factor 3:1
Connection
IEC C19 × 1 (Power Share)
Terminal × 1,
C13 × 6, C19 × 2
IEC C19 × 1 (Power Share)
Terminal × 1,
C13 × 6, C19 × 4
Electrical output supply
system
TT, TN
Efciency
Online Mode
Up to 95.5%
ECO Mode
Up to 99%