SOFAR 1.1K~3KTL User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd
decrease the temperature.
The inverter has
derated because
of the grid
frequency is too
high
Inverter automatically reduce the output
power when the frequency of electrical grid
is too high.
The inverter has
derated by the
Remote control
Inverter records ID83 in case of remote
power derating operation. Check the wiring
of remote input and output control signal
port on the communication board according
to Section 4.5 of this user manual.
The inverter has
shut down
because by the
Remote control
Inverter records ID84 in case of remote
shutdown operation. Check the wiring of
remote input and output control signal port
on the communication board according to
Section 4.5 of this user manual.
Software
version is not
consistent
The software
between the
control board and
the
communication
board is not
consistent
Contact technical support to upgrade
software.
Communicatio
n board
EEPROM fault
The
communication
board EEPROM
is fault
ID95~ID96 are internal faults of inverter,
turn OFF the “DC switch”, wait for 5
minutes, then turn ON the “DC switch”.
Check whether the fault is rectified. If no,
please contact technical support.
Check the country setting according to
Section 6.3 (C)
5.Country of this user manual, If it’s
incorrect, change
it according to Section 6.3 (A) 4.Set
Country Code of
this manual.
Please replace the SD card.
Inverters generally do not need any daily or routine maintenance. Heat sink