7.3.6. DRMS Settings7.3.6. DRMS Settings
After logging into the WEB interface, click “Plant Manage” —— “DRMS Settings”
to enter the interface. After setting, click “Write” to set successfully.
Parameter name Setting instructions
DRM enable
On: general enable switch
O: all DRM settings are disabled.
DRM0 enable
On: receive a DRM0 command from the DRED unit to shut
down the system or return the system to grid connection.
O: No orders are given.
DRM5/6/7/8 percenta-
ge (%)
Receive DRM5/6/7/8 commands from the DRED unit to set
the percentage of the system generating power limit.
7.3.7. Plant Switch Control7.3.7. Plant Switch Control
After logging in the WEB interface, click “Plant Manage”——”Plant Switch Con-
trol” to enter the interface. Select “On” for Plant Switch Status, then click “ON”
or “OFF”, and then click “Write” after setting.
Parameter name Setting instructions
Plant Switch Control
ON: the CH1000 sends a command to power on all inverters.
OFF: the CH1000 sends a command to power o all inverters.
7.3.8. Night Running Control7.3.8. Night Running Control
After logging into the WEB interface, click “Plant Manage”——”Night Running
Control” to enter the interface. After setting, click “Write” to set successfully.
Parameter name Setting instructions
Night running control
On: the inverters that control the entire system do not go o-grid
at night. This control function can be turned on when the system
needs to perform reactive power compensation at night in some
specic application scenarios.
O: the system does not perform reactive power compensation
at night, and all inverters go o-grid at night.
46/92 SOFAR CH1000
Parameter Conguration