sites at altitudes of more than 2000 meters above the sea level
sites exposed to direct sunlight or sites where the ambient temperature may exceed
the specified maximum temperatures
near flammable materials or gases or explosive environments
Clearance
Observe the following minimum clearance:
20 cm from all sides of the battery module.
30 cm from another battery module or any heat source, such as water heater unit,
gas-fueled heater, air conditioning unit or any other equipment
100 cm from emergency exits
30 cm from doors
25 cm from windows
20 cm from air vents
20 cm from other devices
WARNING!
Connect no more than 5 batteries per inverter. Use no more than 3 batteries per
battery tower.
NOTE
The distance between the battery tower and
Home Battery 48V Installation Guide MAN-01-00954-1.1
12 Clearance