L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US-
IB00, L20US-IB60, L20US-IB00 UPS
Power Supply Upon BYP SCR Overtemp: Specifies whether to start bypass mode when
over temperature occurs. The default value is Enable.
Bypass Switches Limit: Cross currents occur during the transfer between bypass mode and
normal mode, which impacts the system. This parameter specifies the number of transfers
between bypass mode and normal mode within 1 hour, which ensures system security. The
value can be 3 to 10 and is 10 by default.
EPO Transfers To BYP: Specifies whether transfers to bypass mode when press EPO button.
The default value is Disable.