L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US-
IB00, L20US-IB60, L20US-IB00 UPS
• Float Temp Compen Coeff(V/Cell/℃): Modify the voltage of compensation after
enable the switch. the value can be 0.001~0.007/cell and is 0.003 by default.
• Boost Charge Setting: Boost charge disable or enable; and is enabled by default.
• No Battery Warning: can be no warning when no batter after set disable, and is enabled
by default.
4.3.7.5. Dry contact setup
INPUT dry contact: Contains a total of 4 input dry contacts. User can choose different
function for IN 01~04.
Each dry contact has 15 functional options, including INV ON, INV OFF, BATT Fault,
Generator, User Alarm3, User Alarm4, Forbidden ECO, Force INV OFF, Input Switch,
Bypass Switch, BATT Switch, BATT Trip, BATT Ground, Thunder, EPO, Close.
IN 01: The default value is INV ON.
IN 02: The default value is INV OFF.
IN 03: The default value is Close.
IN 04: The default value is Close.