L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US-
IB00, L20US-IB60, L20US-IB00 UPS
Chg. Cur. Limiting Coef.: The charging current limit is a multiple of the battery capacity.
The value can be 0.050.15 and is 0.1 by default.
Cell float volt: The float voltage value can be 2.20-2.29 V/cell and is 2.25 V/cell by
default.
Cell boost volt: The battery equalized voltage value can be 2.302.40 V/cell and is 2.30
V/cell by default.
Aver charging Duration: boost charge time limit, the value can be 1999 min, and is 240
by default.
EOD Battery Volt(V/Cell): End of discharge voltage. The value can be 1.60~1.90 and is
1.80 by default.