L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US-
IB00, L20US-IB60, L20US-IB00 UPS
4.3.7.4. Battery setting
• Battery Group: Must modify the number to actual configuration. The value can be 1~8,
default value is 1.
• Battery number: Must modify the number to actual configuration; the value can be
16~26, default value is 20 (for L10/15/20US-IB00).
• Single Battery Capability: Must modify the value to actual configuration. The value can
be 7~2000.
• Boost/Float Conversion(month): Set up boost charge and float charge conversion time.
The value can be 0~24, default value is 0.