L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40, L15US-IB60 L15US-
IB00, L20US-IB60, L20US-IB00 UPS
OUTPUT dry contact: Contains a total of 4 input dry contacts. User can choose different
function for IN 01~04. And choose Normally Closed/ Normally Opened, the default value is
Normally opened.
Each dry contact has 15 functional options, including UPS Warning, Online Mode,
Battery Mode, Bypass Mode, INV Overload, Fan Fault, BATT Fault, BATT Disconnect,
BATT Low Volt, Mains Abnormal, BYP Not Available, EPO, Maint Mode, Parallel Comm
Fault, ECO Mode, Close.
OUT 01: The default value is UPS Warning.
OUT 02: The default value is Bypass Mode.
OUT 03: The default value is BATT Low Volt.
OUT 04: The default value is Online Mode.