Operation Method
Ÿ Error Logs
The Error log contains error information happened. It can record six items at
most. Press ”Up“ and “Down button to review parameter. Long press to Up
return to .the main interface
Ÿ About
This interface shows information of the inverter, include “Product SN”,
“Master, “Manager and “Internal Code”.
Error Logs
>
No error
About
Product SN:
XXXXXXXXXXXXXX
Troubleshooting
68 69
8 Troubleshooting
8.1 Troubleshooting
This section contains information and procedures for solving possible
problems with the series inverters, and provides you with troubleshooting
tips to identify and solve most problems that could occur with the series
inverters.
This section will help you narrow down the source of any problems you may
encounter. Please read the following troubleshooting steps.
Check warnings or fault messages on System Control Panel or Fault codes
on the inverter information panel. If a message is displayed, record it before
doing anything further.
Attempt the solution indicated in below table.
Faults
Diagnosis and Solution
TzFault
Over Current Fault.
-Wait for about 10 seconds to check if the inverter is back
to normal.
-Disconnect the DC switch and restart the inverter.
-Or seek help from us.
GridLostFault
Grid Lost Fault.
-Check if the mains cable is loose.
-Wait for a while and the system will reconnect when the
utility is back to normal.
-Or seek help from us.
GridVoltFault
Grid Voltage Out of Range.
-Check if the mains cable is loose.
-Wait for a while and the system will reconnect when the
utility is back to normal.
-Or seek help from us.
GridFreqFault
Grid Frequency Out of Range.
-Wait for a while and the system will reconnect when the
utility is back to normal.
-Or seek help from us.
PvVoltFault
PV Voltage Fault.
-Check whether the PV is overvoltage.
-Or seek help from us.
BusVoltFault
DC Bus Voltage Out of Normal Range.
-Check if the PV input voltage is within the operating
range of the inverter.
-Disconnect PV wiring and reconnect.
-Or seek help from us.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Solax X3-PRO G2 Series and is the answer not in the manual?

Solax X3-PRO G2 Series Specifications

General IconGeneral
ModelX3-PRO G2 Series
CategoryInverter
MPPT Efficiency99.9%
Max. DC Voltage1100V
THDi<3%
DC SwitchYes
European Efficiency98%
CommunicationWiFi, Ethernet, RS485
Operating Temperature Range-25°C to +60°C
AC Voltage Range310V-480V
AC Grid Frequency50/60 Hz
Warranty10 years
Rated Power6kW, 8kW, 10kW, 12kW, 15kW, 20kW, 25kW, 30kW
Number of MPPTs2 or 4 (depends on model)
AC Output Power6kW / 8kW / 10kW / 12kW / 15kW / 20kW / 25kW / 30kW
Nominal AC Voltage400V
ProtectionDC Reverse Polarity Protection, AC Short Circuit Protection, Output Over Current Protection, Output Over Voltage Protection