Connection Steps
6.2 Grid Connection
The series inverter are designed for three phase grid. For the rated grid voltage
and frequency, please refer to the section “Technical Data”. Other technical
requests should comply with the requirement of the local public grid.
Micro-breaker should be installed between inverter and grid, any loads should
not be connected with inverter directly.
Note: Check the grid voltage and compare with the permissive voltage range
(refer to technical data).
a) Disconnect the circuit-bricker from all the phases and secure against re-
connection.
b) Select appropriate cable and prepare to strip the wires:
- Strip 82 mm of insulation from the cable end.
- Use the stripping pliers to strip 12 mm of insulation from wire ends as below.
Table: Cable and Micro-breaker Recommended
Incorrect Connection between Loads and Inverter
L1, L2, L3 Cable
PE, N Cable
5-6 mm²
Model
5-6 mm²
*The cable size and conductor material of the PE/N / L1/L2/L3 should be the same.
The parameters have some differences because of different environment and material. Please
choose appropriate cable and micro-breaker according to the local conditions.
5-6 mm²
c) Fetch the AC waterproof cover from the carton.
Micro-breaker
20 A
32 A
X3-PRO-8K-G2(2D) X3-PRO-10K-G2(2D) X3-PRO-15K-G2(2D) X3-PRO-12K-G2(2D)
20 A 25 A
6-8 mm²
5-6 mm²
40 A
L1 L2 L3
N PE
X3-PRO-17K-G2(2D) X3-PRO-20K-G2(2D)
strip length
L1
L2
L3
82 m m
12 m m
d) Unscrew the fastening nut of the AC waterproof cover and remove the
sealing rings. Select appropriate number of the sealing rings according to
the outer diameter of the cable. Let the cable pass through the fastening
nut, the sealing ring(s) and the waterproof cover in sequence.
a
b
Diameter(mm)
Sealing ring(s)
a
a+b12~18
18~25
diameter
L1, L2, L3 Cable
PE, N Cable
Model
5-6 mm²
8-10 mm²
Micro-breaker
32 A
50 A
X3-PRO-30K-G2(3D) X3-PRO-25K-G2(3D)
6-8 mm²
40 A
10 mm²
63 A
X3-PRO-20K-G2(3D)X3-PRO-17K-G2(3D)X3-PRO-15K-G2(3D)
6-8 mm²
40 A
6-8 mm²
40 A
L1, L2, L3 Cable
PE, N Cable
Model
Micro-breaker
8-10 mm²
50 A
10 mm²
63 A
X3-PRO-10K-G2-LV X3-PRO-12K-G2-LV X3-PRO-15K-G2-LV
6 8 mm- ²
40 A
30 31
Electrical Connections Electrical Connections
5-6 mm²
5-6 mm²
5-6 mm² 6-8 mm²
5-6 mm²
6-8 mm²
5-6 mm² 8-10 mm²6-8 mm² 10 mm²6-8 mm²
8-10 mm² 10 mm²6 8 mm- ²