2.2 Important Safety Instructions
Danger!
Danger to life due to high voltages in the inverter!
All work must be carried out by qualified electrician.
The appliance is not to be used by children or persons with
reduced physical sensory or mental capabilities, or lack of
experience and knowledge, unless they have been given
supervision or instruction.
Children should be supervised to ensure that they do not play
with the appliance.
Caution!
Possible damage to health as a result of the effects of
radiation!
Do not stay closer than 20 cm to the inverter for a long time.
Note!
Grounding the PV generator.
Comply with the local requirements for grounding the PV
modules and the PV generator. It is recommended to connect
the generator frame and other electrically conductive surfaces
in a manner which ensures continuous conduction and
ground these in order to have optimal protection of system
and persons.
Warning!
Ensure input DC voltage Max. DC voltage. Over voltage
may cause permanent damage to inverter or other losses,
which will not be included in warranty!
Warning!
Authorized service personnel must disconnect both AC and
DC power from the inverter before attempting any
maintenance or cleaning or working on any circuits connected
to the inverter.
Prior to the application, please read this section carefully to ensure correct
and safe application. Please keep the user manual properly.
Use only attachments recommended. Otherwise may result in a risk of fire,
electric shock, or injury to person.
Make sure that existing wiring is in good condition and that wire is not
undersized.
Do not disassemble any parts of inverter which are not mentioned in
installation guide. It contains no user-serviceable parts. See Warranty for
instructions on obtaining service. Attempting to service the inverter yourself
may result in a risk of electric shock or fire and will void your warranty.
Keep away from flammable, explosive materials to avoid fire disaster.
The installation place should be away from humid or corrosive substance.
Authorized service personnel must use insulated tools when installing or
working with this equipment.
PV modules shall have an IEC 61730 class A rating.
Never touch either the positive or negative pole of PV connecting device.
Strictly prohibit touching both of them at the same time.
The unit contains capacitors that remain charged to a potentially lethal
voltage after the MAINS and PV supply have been disconnected.
Hazardous voltage will present for up to 5 minutes after disconnection from
power supply.
CAUTION - RISK of electric shock from energy stored in capacitor. Never
operate on the solar inverter couplers, The MAINS cables, PV cables or the
PV generator when power is applied. After switching off the PV and Mains,
always wait for 5 minutes to let the intermediate circuit capacitors discharge
before you unplug DC and MAINS couplers.
When accessing the internal circuit of solar inverter, it is very important to
wait 5 minutes before operating the power circuit or demounting the
electrolyte capacitors inside the device. Do not open the device before hand
since the capacitors time to sufficiently discharge! require
Measure the voltage between terminals UDC+ and UDC- with a multi-meter
(impedance at least 1 Mohm) to ensure that the device is discharged before
beginning work (35 VDC) inside the device.
Safety Safety
Do not operate the inverter when the device is running.
Risk of electric shock!
Caution!
Danger of burn injuries due to hot enclosure parts!
During operation, the upper lid of the enclosure and the
enclosure body may become hot.
If necessary, touch the lower temperature enclosure lid during
operation.
Warning!
Warning!
06 07

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Solax X3-PRO G2 Series and is the answer not in the manual?

Solax X3-PRO G2 Series Specifications

General IconGeneral
ModelX3-PRO G2 Series
CategoryInverter
MPPT Efficiency99.9%
Max. DC Voltage1100V
THDi<3%
DC SwitchYes
European Efficiency98%
CommunicationWiFi, Ethernet, RS485
Operating Temperature Range-25°C to +60°C
AC Voltage Range310V-480V
AC Grid Frequency50/60 Hz
Warranty10 years
Rated Power6kW, 8kW, 10kW, 12kW, 15kW, 20kW, 25kW, 30kW
Number of MPPTs2 or 4 (depends on model)
AC Output Power6kW / 8kW / 10kW / 12kW / 15kW / 20kW / 25kW / 30kW
Nominal AC Voltage400V
ProtectionDC Reverse Polarity Protection, AC Short Circuit Protection, Output Over Current Protection, Output Over Voltage Protection