5. Operation 5. Operation
5.6.7.2 ON/OFF
Figure 5.46 ON/OFF
Settings
ON/OFF
2015-02-23 19 35
ON
OFF
Y E S =< E N T > N O = < E S C >
Enable/Disable the function.
.This function should be activated only after the installation In the case of a low battery
voltage shutdown, the inverter will shut-down. This setting can be enabled, so when the
inverter detects PV or grid it wakes up the battery. This function conflicts with the battery
reverse polarity protection( If the installer connects cables with wrong polarity the inverter ,
can protect itself from damage).To avoid the possible damage during installation do not ,
active battery wakeup function before finishing the first commissioning.
5.6.6.5 Battery Wakeup
5.6.7 Export power Set
Settings
Figure 5.44 Export power Set
Export power Set
2015-02-23 19 35
BackflowPower
ON/OFF
FailSafe ON/OFF
Figure 5.45 Backflow Power
Settings
Backflow Power
2015-02-23 19 35
Y E S =< E N T > N O = < E S C >
Backflow Power:+1200W
E S C
U P
D O W N E N T
Determine the allowed backfeed power. (System export to the grid)
5.6.7.1 Backflow Power
This function is to set the export power control.
1.Backflow Power. 2. ON/OFF. 3.Failsafe ON/OFF
Setting 1&3 are only valid when Setting 2 is set to "ON"