EasyManua.ls Logo

Soltaro Hyper Series - 9 Technical Data; Hyper 2000;3000

Soltaro Hyper Series
47 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
40
9. Technical Data
9.1 Hyper 2000/3000
PV Inputs
Hyper 2000
Hyper 3000
Max. PV-generator power
2500W
3300W
Max. PV voltage
550V d.c.
Rated PV Voltage
360V d.c.
MPPT Voltage Range
125~500V d.c.
PV Start Voltage
100V d.c.
Max. PV current
12A d.c.
Max. Short Circuit Current
15A d.c.
Strings per MPP Tracker
2
Number of MPP Trackers
1
Galvanic Isolation for PV
Modules
Transformerless
Reverse Current to PV Panels
No
AC Ratings
Hyper 2000
Hyper 3000
Rated AC Power
2000VA
3000VA
Rated AC Voltage
230V a.c.
AC Voltage Range
180V~264V a.c.
Rated AC Frequency
50Hz/60Hz
Max. AC Current to Grid
(Feed Back Current)
8.7A a.c.
13A a.c.
Max. AC Current from Grid
(Bypass + Grid Charge)
17.4A a.c.
26A a.c.
Max. Output Overcurrent
Protection
25A a.c.
32A a.c.
Power Factor Range
-0.8~+0.8
Total Harmonic Distortions (i)
<3%
Inrush Current
(Peak/Duration)
120A/32us
Max. Output Fault Current
(Peak/Duration)
200A/10ms
EPS Ratings
Hyper 2000
Hyper 3000
EPS Rated Power
2000VA
3000VA
Overload Capacity
1.1 x Pnom, 10 sec; 1.5 x Pnom, 100 ms
EPS Rated Voltage
230V a.c.
EPS Rated Frequency
50Hz / 60Hz
EPS Rated Current
8.7A
13A
Changeover Time
<2s in EPS Mode, 10~20ms in UPS Mode
Total Harmonic Distortion (V)
< 3%
Parallel Operation
No