5.1.3 FOLLOW ZONES
Sections [001] - [016] = Zones 1 - 16: First Digit = 3
When an armed Follow Zone opens, the control panel will immediately generate an alarm, unless an Entry
Delay zone opens first:
• If an armed Follow Zone opens after an Entry Delay zone opens, the control panel waits until the Entry
Delay Timer has elapsed before generating an alarm.
• If an armed Follow Zone opens after more than one Entry Delay zone opens, the control panel will wait
until the Entry Delay Timer of the zone that opened first has elapsed.
This feature is commonly used when a motion detector is protecting the area occupied by the entry point
keypad. This will prevent the motion detector from causing an alarm when a user enters through the entry
point to disarm the system. Also, refer to Zone Speed on page 25.
5.1.4 I
NSTANT
Z
ONES
Sections [001] - [016] = Zones 1 - 16: First Digit = 4
When an armed Instant Zone opens, the control panel immediately generates an alarm. Instant Zones are
commonly used for windows, patio doors, skylights and other perimeter type zones. Also, refer to Zone
Speed on page 25.
5.1.5 24H
R
. B
URGLARY
Z
ONES
/ F
IRE
Z
ONE
/ K
EYSWITCH
Z
ONE
Sections [001] - [016] = Zones 1 - 16: First Digit = 5
24Hr. Burglary Zones
Whenever a 24Hr. Burglary Zone opens, whether the
system is armed or disarmed, the control panel will
immediately generate an alarm. Also, refer to Zone
Speed on page 25.
Keyswitch Zone
If
zone 2
is defined as a 24Hr. Burglary Zone it
immediately becomes a Keyswitch Zone (first digit in
section [002] = 5). Connecting a keyswitch to zone 2 allows
users to arm the system by pressing a button or by turning
a switch on or off. Please refer to Keyswitch Connections
on page 10 and to Keyswitch Options on page 24.
Standard 24Hr. Fire Zone
If zone 3 is defined as a 24Hr. Burglary Zone, it
immediately becomes a Standard 24Hr. Fire Zone (first
digit in section [003] = 5). For information on how to
connect smoke detectors to the control panel, refer to
Fire Circuits on page 12. Whenever a Standard 24Hr.
Fire Zone opens, whether it is armed or disarmed, the
control panel will generate the following:
• The control panel can send the Zone 3 Alarm report
code programmed in section [187].
• If a tamper/wiring fault occurs on a Fire Zone, the
control panel can send a Fire Loop Trouble report
code programmed in section [206] to the Central
Station. A Fire Loop Trouble will also appear in the
keypads’ Trouble Display (see page 54).
• Alarms are always audible, regardless of other set-
tings. Fire alarms will generate an intermittent (pulsed)
bell/siren output signal as demonstrated in Figure 5-2.
Delayed Fire Zone
is triggered
Activate bell/siren output & delay
report transmission for 30 seconds.
Yes
Any key on
keypad pressed
within 30
seconds?
De-activate bell/siren output and
delay report transmission an
additional 90 seconds.
Problem
corrected?
Latch alarm and
transmit report code
(see section 5.1.5 of
this manual).
END
Alarm Disabled
Yes
Yes
No
Problem
corrected within
30 seconds?
Yes
No
No
gure
-
:
e
aye
r.
re
one
gure
-
:
e
u
pu
ur
ng
re
arm