SPECTRA SERIES 29
PART 7: ALARM OPTIONS
7.1 BELL CUT-OFF TIMER
Section [073] = Partition 1, [074] = Partition 2: 000 = Disabled, 001-255 minutes, Default = 4 min.
After an audible alarm, the bell or siren will stop upon disarming of the partition or when the Bell Cut-Off Timer has
elapsed, whichever comes first.
7.2 RECYCLE ALARM
Once the Bell Cut-Off Timer has elapsed and after the Recycle Delay has elapsed, the control panel will re-verify the
zone status and if there are any open zones, the control panel will generate another alarm. In one armed period, the
control panel will repeat this sequence the number of times defined by the Recycle Counter.
7.2.1 R
ECYCLE
A
LARM
D
ELAY
Section [090]: 000 = disabled, 001-255 minutes, Default = disabled
The Recycle Delay determines the amount of time after Bell Cut-Off that the control panel will wait before
re-verifying zone status.
7.2.2 R
ECYCLE
C
OUNTER
Section [091]: 000 = disabled, 001-255, Default = disabled
The Recycle Counter determines the number of times you wish the control panel to re-verify the zone
status after Bell Cut-Off in one armed period.
7.3 TAMPER RECOGNITION
Section [132] - Zone Options
[1] OFF / [2] OFF - Tamper Recognition Disabled (default)
The control panel will not perform any action other than generate a standard alarm when a tamper or wire fault
occurs in an armed system. If the system is disarmed, the control panel will display the zone as open in the keypad
display but will not generate an alarm. This option is not permitted on UL systems.
[1] OFF / [2] ON - Trouble Only
When a tamper wiring failure occurs on a zone in a disarmed system, a Tamper/Zone Wiring Failure will appear in
the keypads’ Trouble Display (see page 54) and the control panel will transmit the appropriate Zone Tamper report
code (see page 33). When a tamper wiring failure occurs on a zone in an armed system, the control panel will
follow the zone's Alarm Types setting (see page 24).
[1] ON / [2] OFF - Silent Alarm
In a disarmed system, it functions the same as the "Trouble Only" setting, but it will also generate a silent alarm. A
silent alarm will not trigger any bells or sirens but the system will have to be disarmed. When a tamper wiring failure
occurs on a zone in an armed system, the control panel will follow the zone's Alarm Types setting (see page 24).
[1] ON / [2] ON - Audible Alarm
In a disarmed system, it functions the same as "Trouble Only" setting, except it will also generate an audible alarm.
When a tamper wiring failure occurs on a zone in an armed system, the control panel will follow the zone's Alarm
Types setting (see page 24).
7.3.1 T
AMPER
B
YPASS
O
PTIONS
Section [132] - Zone Options
Option [3] OFF = Will generate a tamper if detected on a bypassed zone (default)
Option [3] ON = Tampers on bypassed zones will be ignored
With option [3] on, the Tamper Recognition feature follows the zone bypass definition. This means the
control panel will ignore any tampers detected on a bypassed zone. With option [3] off, Tamper Recognition
ignores the bypass definition. This means the control panel will generate an incident as per Tamper
Recognition settings if a tamper or wire fault occurs on a bypassed zone.