SPECTRA SERIES 37
8.9 BELL ON COMMUNICATION FAILURE
Section [135] - Dialer Options
Option [6] OFF = Bell On Communication Failure Disabled (default)
Option [6] ON = Bell On Communication Failure Enabled
If the control panel fails to communicate with the central station when the system is armed, it will enable the
BELL
output, setting off any bells or sirens connected to the output.
8.10 DIAL TONE DELAY
Section [136] - Dialer Options
Option [5] OFF = Dialer will continue to dial if no dial tone is present after 4 seconds (default).
Option [5] ON = Dialer will hang-up if no dial tone is present after 16 seconds
8.11 MAXIMUM DIALING ATTEMPTS
Section [081]: 001-016 attempts, Default = 8 attempts
The value programmed here determines how many times the control panel will re-dial the same Central Station
Telephone Number before proceeding to the next number.
8.12 DELAY BETWEEN DIALING ATTEMPTS
Section [082]: 000-255 seconds, Default = 20 seconds
This delay determines the amount of time the control panel will wait between each dialing attempt.
8.13 ALTERNATE DIAL OPTION
Section [136] - Dialer Options
Option [4] OFF = Alternate Dial Disabled (default)
Option [4] ON = Alternate Dial Enabled
With option [4] off, the control panel will dial the back up telephone number programmed in section [153] after all
attempts to one Central Station Telephone Number have failed (see Maximum Dialing Attempts on page 37). With
option [4] on, the control panel will dial the back up telephone number after every failed attempt.
8.14 RECENT CLOSE DELAY
Section [085]: 000-255 seconds, Default = no delay
If after having armed the system, an alarm is generated within the period defined by the Recent Close Delay, the
control panel will attempt to transmit the Recent Close report code programmed in section [195].
8.15 AUTO TEST REPORT
Sections [087]: 000=disabled, 001-255 days, default = disabled Section [110]: Time (HH:MM)
The control panel will transmit the Test Report report code programmed into section [211] after the number of days
programmed into section [087] has elapsed and at the time programmed into section [110]. Use the 24 hour clock to
program the time (i.e. 6:30PM = 18:30). After programming these sections, the control panel will only begin
transmitting the Test Report code after Midnight of the first day.
8.16 POWER FAILURE REPORT DELAY
Section [086]: 001-255 minutes, default = 15 minutes
The control panel will transmit the AC Failure report code programmed in section [205] after the Power Failure
Report Delay period has elapsed.