8.2.10 SYSTEM TROUBLE REPORT CODES
Section [205] - [207]
Whenever the system generates one of the instances listed below, the control panel can send the
appropriate report code to the central station, identifying the type of system trouble.
__/__
AC FAILURE
: The control panel has detected a loss of AC power. Transmission of this report code
can be delayed (see Power Failure Report Delay on page 37).
__/__
BATTERY FAILURE
: Back up battery is disconnected or battery voltage is 10.5V.
__/__
AUXILIARY SUPPLY
: Auxiliary power supply has overloaded (current consumption is >1.1A).
__/__
BELL
OUTPUT
OVERLOAD
: Bell/siren output has overloaded (see page 9).
__/__
BELL
OUTPUT
DISCONNECTED
: Devices connected to the Bell Output have been disconnected.
__/__
TIMER
LOSS
: The control panel has detected a loss in time or clock failure (see page 41)
__/__
FIRE
LOOP
TROUBLE
: The control panel has detected a tamper trouble on a fire zone.
__/__
WIRELESS
LOW
BATTERY
: The battery voltage of a Liberator wireless transmitter (motion detector or
contact switch) has dropped to below 6.5V.
__/__
MODULE
FAULT
: All keypads connected to the control panel have been disconnected. If Zone
Expansion Module Supervision has been enabled (see page 43) and the Zone Expansion Module
has been disconnected. If Wireless Bus Module Supervision has been enabled (see page 43) and
the Liberator Wireless Bus Modules has been disconnected.
__/__
PRINTER FAULT
: An error has occurred on the Printer Module.
__/__
FAIL TO COMMUNICATE
: The control panel has failed all attempts to communicate with the central
station. The report code will be transmitted upon the next successful attempt.
8.2.11 SYSTEM TROUBLE RESTORE CODES
Sections [208] - [210]
Whenever the system restores one of the troubles listed in section 8.2.10, the control panel can send the
appropriate report code to the central station, identifying the type of system trouble restore. If Telephone
Line Monitoring is enabled (see page 38), the control panel can also transmit a TLM Restore report code.
8.2.12 SPECIAL REPORTING CODES
Sections [211] - [213]
Whenever the system generates one of the instances listed below, the control panel can send the
appropriate report code to the central station, identifying the type of system occurrence.
__/__
COLD START
: The control panel was completely shutdown (no battery, no AC), then the control panel
was re-started
__/__
TEST REPORT
: A test report has been generated automatically (see page 37).
__/__
PC
CALL BACK
: See page 46.
__/__
PC ACCESS
: The control panel has established communication with the PC software.
__/__
INSTALLER
IN
: Installer has entered the programming mode.
__/__
INSTALLER
OUT
: Installer has exited the programming mode.
__/__
TX
SUPERVISION
LOSS
: Wireless Transmitter Supervision (see page 47) has been enabled and a
transmitter is no longer communicating with the system.
__/__
TX
SUPERVISION
RESTORE
: When the above trouble has been restored
8.3 CENTRAL STATION TELEPHONE NUMBERS
Section [151] = Phone#1, [152] = Phone#2, [153] = Back-up Phone#: Up to 32 digits
The Spectra Control Panels can dial up to 2 different central station telephone numbers. You can enter any digit from 0 to 9
and any special keys or functions (see Table 5 on the next page) up to a maximum of 32 digits. For more information on
how these telephone numbers are used, please refer to Event Call Direction on page 36 & Reporting Formats on page 35.
After the Maximum Dialing Attempts (see page 37) to one central station telephone number have failed, the control panel
will then dial the back up telephone number. If the Alternate Dial Option (see page 37) is enabled, the control panel will dial
the programmed back up telephone number after every failed attempt. If no back up telephone number is programmed, the
control panel will never report to the back-up telephone number. Also refer to Delay Between Dialing Attempts on page 37.