18
2.7 Alarm / Error display messages
If an error occurs, the details of the error or alarm will appear on a message screen, which
can be accessed by scrolling through the run menu. Pressing and holding the
OK
button for
3 seconds can clear a message and re-energize the alarm relay(s). If the cause has not been
corrected, the same message will reappear. If the error or alarm is of a latching type, only
the message will disappear. The alarm relay will remain de-energised until the correct pass
code is entered in the commissioning menu. If more than one error or alarm has occurred,
the next message will appear (in priority order) after the previous one has been cleared.
See Section 9 - 'Fault finding'.
2.8 Equipment delivery, handling and storage
Factory shipment
Prior to shipment, the product is tested, calibrated and inspected to ensure proper operation.
Receipt of shipment.
Each carton should be inspected at the time of delivery for possible external damage. Any
visible damage should be recorded immediately on the carrier’s copy of the delivery slip.
Each carton should be unpacked carefully and its contents checked for damage. If it is found
that some items have been damaged or are missing, notify Spirax Sarco immediately and
provide full details. In addition, damage must be reported to the carrier with a request for
their on-site inspection of the damaged item and its shipping carton.
Storage
If the product is to be stored for a period prior to installation, the environmental storage
conditions should be at a temperature between 0 °C and 65 °C (32 °F and 149 °F), and
between 10% and 90% relative humidity (non-condensing).
Before installing and connecting the power ensure there is no condensation within the unit.
Operators instructions
An alternative operator instruction manual, in place of this manual, for operating the equipment
is required. This will avoid the commissioning menu passcode being disclosed to the operator.
The alarm reset passcode may optionally be disclosed if this is deemed necessary.