EasyManuals Logo

Spirax Sarco LC2650 User Manual

Spirax Sarco LC2650
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #43 background imageLoading...
Page #43 background image
IM-P402-128 EMM Issue 7
43
ä
ä
ä
OUTPUT
DRIVE
CONTROL
OUTPUT
DRIVE
ACTION
OUTPUT
DRIVE
TYPE
ä
OUTPUT
DRIVE
DEADBAND
6.5.6 OUTPUT DRIVE sub-menu
Sets type of valve control - ON OFF or PROP
(proportional).
Selects PUMP IN or PUMP OUT, i.e. fill or empty control.
Only available if proportional control is selected. Selects
method of valve actuator operation - Valve Motor Drive
(VMD), or 4-20 mA.
Only available if proportional control is selected. A wider
DEADBAND is set for more turbulent water conditions. Set
to 10% as a starting point.
Note: Grey tint indicates features only available under certain conditions.