IM-P402-128 EMM Issue 7
61
LEVEL - CTL BAND (Control Band)
Ranges
5 - 100 (Interactive with steam offset and SP. control band
cannot exceed 100%)
Default 20
Resolution (steps) 1
Units %
LEVEL - SP (Set Point)
Ranges
3 - 97 (Interactive with steam offset and SP. control band
cannot exceed 100%)
Default 50
Resolution (steps) 1
Units %
STEAM - OFFSET (% increase in water level due to 100% steam demand)
Ranges
0 - 94 (Interactive with steam offset and SP. control band
cannot exceed 100%)
Default 0
Resolution (steps) 1
Units %
STEAM - MAX (Scale steam meter output to maximum steam load)
Ranges 10 - 100%
Default 100
Resolution (steps) 1
Units %
WATER METER (Feedwater flowmeter)
Ranges OFF or ON
Default OFF
WATER METER - ON - MAX (Scale steam meter output to maximum feedwater flow)
Ranges 10 - 100%
Default 100
Resolution (steps) 1
Units %