10.8.3 OUTPUT MENU
COMMS - ADDRESS (MODBUS communication)
DRIVE - CONTROL
Ranges PROP or ON/OFF
Default PROP
DRIVE - ACTION
Ranges PUMP IN or OUT
Default PUMP IN
DRIVE - TYPE
Ranges VMD or 4-20 mA
Default VMD (Valve Motor Drive)
DRIVE - DEADBAND
Ranges 5 - 20 (Relay hysteresis = 1%)
Default 10
Resolution (steps) 1
Units %
RETRANS - 0 or 4 mA
Ranges 0 or 4 mA
Default 4 mA
RETRANS - SET - 4 mA
Ranges 0 - 100
Default 0
Units %
RETRANS - SET - 20 mA
Ranges 0 - 100
Default 100
Units %
RETRANS - CHECK - 4 mA
Default 4.00
Resolution (steps) 0.01
Units mA
RETRANS - CHECK - 20 mA
Default 20.00
Resolution (steps) 0.01
Units mA