63
POSITION (positioner) - 0 or 4 mA
Ranges 0 or 4 mA
Default 4 mA
POSITION (positioner) - SET - 4 mA
Ranges 0 - 100
Default 0
Units %
POSITION (positioner) - SET - 20 mA
Ranges 0 - 100
Default 100
Units %
POSITION (positioner) - CHECK - 4 mA
Default 4.00
Resolution (steps) 0.01
Units mA
POSITION (positioner) - RETRANS - CHECK - 20 mA
Default 20.00
Resolution (steps) 0.01
Units mA
COMMS - ADDRESS
Ranges 001 - 247
Default 001
COMMS - BAUD
Ranges 1200, 9600 or 19200
Default 9600
Units BAUD or bits/second
COMMS - IR (Infrared)
Ranges MASTER or SLAVE
Default SLAVE
COMMS - IR UNITS IN NETWORK
Ranges 1 - 8
ALARM 1 or 2 MENU
HI or LO
Ranges HIGH or LOW
Default HIGH (alarm 1) and LOW (alarm 2)