EasyManua.ls Logo

Spirax Sarco SP500 - Sp500 Menu

Spirax Sarco SP500
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IM-P343-35 CTLS Issue 5
37
SP500 Electropneumatic Smart Positioner
Clear stored
values
(RESET)
Recall stored
values
(RETRN)
Retain temporary
values
(RTAIN)
Mounting position
check
(CALIB)
Fig. 53
Software
version
(Ver X.XX)
SET-UP
NOW
From RETRN
SP500
MENU
3 seconds enter
3 seconds enter
9.2 SP500 MENU
Programming notes
You are now in SP500 MENU.
SP500 functions include:
1. Visualisation of the embedded software version (VER--).
2. Positional setting (CALIB).
3. Resetting of programmed values to default settings (RESET).
4. To retain settings in the temporary memory (RTAIN).
5. Returning to previously stored settings (RETRN).
To check the setting (CALIB) press and hold
key for 3 seconds. The display will count down the 3 seconds.
CALIB also provides access to RESET/RTAIN/RETRN functions.
To view the embedded version of software (VER-.--) press
key.
To advance to manual operation (MANOP) press key.
9.2.1 VER -.-- software version
Programming notes
To view the version of the embedded software (VER-.--) press key.
Press key to return to SP500 MENU.
The display will automatically return to SP500 MENU after 10 seconds.

Related product manuals