Connection to central heating radiators with supplementary boiler and sanitary water combined with
solar panel.
Figure 55 – Connection to central heating radiators with another boiler support and sanitary water combined with solar panel
Note:
- The Differential thermostat must have a hystersis of 15 to 25 °C.
- Water temperature controlled regulation "Off" put the boiler in "manual" mode and power level to "5"
- Modulating pump "On"
- Water sensing inhibition "On"
- Alternative hydro shutdown "On"
- Pump "On" = 50 °C
- Pump "Off" = same or thermostat temperature 1°C below the temperature differential thermostat
When using the generator with differential thermostat the machine must be connected in the CONNECTION "Remote".
Calculation deposits of inertia / buffer tank: for pellet boilers it is recommended that the buffer tank has 20l/kW.
Connecting underfloor heating in conjunction with another boiler support and sanitary water combined with solar panel
Figure 56
– Connecting underfloor heating in conjunction with supplementary boiler and domestic hot water combined with solar
panel