5. Check that all pins of the AC plug are free of voltage. Use a
suitable voltmeter for this (do not use a simple neon phase
checker).
NOTICE!
Risk of damage to the inverter or derating!
– The mounting location must satisfy the fol-
lowing conditions:
– The mounting location and immediate
environment are permanently fixed, ver-
tical, flat, non-inflammable and not
subject to constant vibration.
– The permissible ambient conditions are
conformed to; see Technical data
Ä
Chapter 8 „Technical data“ on page 57
.
– The following free spaces must be
present around the inverter:
Above/below: at least 200 mm
At the sides/in front: at least 60 mm
– Do not install the inverter in areas where
animals are kept.
– Observe the connection ratings specified on
the type plate.
– The DC cables must not be connected to an
earth potential (DC inputs and AC output
are not galvanically isolated).
NOTICE!
When transmitting data over a public network:
– Transmitting data over a public network may
result in additional costs.
–
Data transmitted over a public network is
not protected from unauthorised access by
third-parties.
Notice
– Avoid exposing the inverter to direct sun-
light.
– The display must be readable on the
installed device.
– The inverter operates not completely noise-
lessly
. Consider this when choosing an
installation location.
EN
750.661 | Z03 | 2016-09-12
31