StecaGrid 5003 StecaGrid 6003
Derating / power limiting occurs automatically when:
n input power > max. recommended PV power
n Cooling is inadequate
n Input current too high
n Output current too high
n Grid frequency too high (in accordance with country
setting)
n Limiting signal on external interface
n Output power limited (set on the inverter)
DC side (storage connection)
1)
Voltage 580 V ... 1000 V
Maximum current 10 A
AC output side (grid connection)
Output voltage 320 V to 480 V (depending on the country settings)
Rated output voltage 400 V
Maximum output current 10 A
Maximum inrush current (switch-
on current)
16 A (for 10 ms)
RMS short-circuit current 3.82 A
RMS
(for 60 ms)
Rated output current 7.2 A 8.7 A
Maximum effective power
(cos φ = 1)
5,000 W 6,000 W
Maximum effective power
(cos φ = 0.95)
4,750 W 5,700 W
Maximum effective power
(cos φ = 0.90)
4,500 W 5,400 W
Maximum apparent power
(cos φ = 0.95)
5,000 VA 6,000 VA
Maximum apparent power
(cos φ = 0.90)
5,000 VA 6,000 VA
Rated output 5,000 W 6,000 W
Nominal frequency 50 Hz and 60 Hz
Grid type L
1
/L
2
/L
3
/N/FE (protective earth)
Grid frequency 45 Hz ... 65 Hz (depending on the country settings)
Power losses in night-time opera-
tion
< 3 W
EN