Secure Menu (Up and Enter - 5 seconds)
Set Point Process
Water
Temp.
Control
Unit
Heat Low
Oil Temp.
Control
Unit
Heat
High
SEC #### Security Code 4 4
FnC HL/HH/L Function (Lo/Hi heat Chiller) HL HL
Sto 0 to 100 Self Tune Offset Percent 0 0
InC -500 to +500 Input Correction 0 0
Fil OFF, 1 to 99 digital Filter value 0=off (electrical noise) OFF OFF
SP2 ### Second Set Pt (COOLING) 0 0
Pd2 On/OFF Link the I and D terms to PB2 ON ON
Art OFF, 1 to 99.99 Approach Rate outside PB1 OFF OFF
tci On/OFF T/C Monitor On/OFF OFF OFF
FLO On/OFF Flow Monitor On/OFF OFF OFF
FCY ### Flow in FREQ.
FSL 0 to 100 Flow Scale Low @ 25 Hz (CAL.) 6 6
FSH 0 to 255 Flow Scale High @ 225 Hz (CAL) 30 30
FLF 0 to 100 Flow Filter 2 2
SAF On/OFF Safety Thermo On/OFF ON ON
PrS On/OFF Pressure Input On/OFF ON ON
InP J-/CA-/E- T/C Input Type (J, K, E) J J
Int OFF,0.1 to 540.0 Input Fault Timer (min.) OFF OFF
Ot1
Output 1 type
OnF On/OFF
S1d #### On/OFF differential
1 to 80t Time proportioning cycle rate in sec. 20 20
#PuL 1 to 7
Pulse curve value 1 = linear, 7 = most non-
linear
PrP Voltage/Current proportional output
Ot2
Output 2 type
OnF ON/Off
S2d #### On/Off differential
1 to 80 Time proportioning cycle rate in sec. 15 15
#PuL 1 to 7
Pulse curve value 1 = linear, 7 = most non-
linear
PrP Voltage/Current proportional output
SEn OFF<1 to 4000 Sensor rate of change (cnts or deg. per sec) OFF OFF
SCL DEFAULTED Scale low 0 0
SCH DEFAULTED Scale high 250 550
SPL min - SCL Set Pt. low limit 0 0
SPH max- SCH Set Pt. high limit 250 550
S1S dir/rE Direct or Reverse Acting rE rE
S1L 0 to 90 Output 1 low limit 0 0
S1H 10 to 102 Output 1 high limit 100 100