TS20C USER MANUAL SECTION 7
120
Compressor Shuts Down With 
Air Demand Present
Loss of control voltage Check incoming power
Low incoming voltage Check control fuses and wiring. Consult power 
company. The Sulliar Supervisor™ will provide 
indication of most maintenance problems if 
control power has not been lost. Shutdowns 
will occur upon a faulty condition or a bad 
sender condition.
Excessive operating pressure Check maximum P2 pressure setting.
HIGH PRESS P1 display; Max P1 pressure 
may be set too low. Consult factory for 
recalibration.
Defective solenoid valve; solenoid valve 
should cause Sullicon Control lever to move to 
unload stop when the unload pressure setting 
P2A is exceeded. Repair if defective.
Defective blowdown valve; blowdown valve 
should exhaust sump pressure to 30 psig (2.1 
bar) for integrated coolers; 50 psig (3.4 bar) for 
remote coolers when maximum operating 
pressure is reached. Repair if defective.
Open or shorted P1, P2, P3 or P4 sender 
message; replace sender indicated.
Operating lever of inlet butterfly valve is loose 
on valve shaft. Reposition the valve plate and 
tighten lever set screw.
HIGH TEMP T1 or T3 Message 
Displayed
Cooling air flow restricted; clean cooler and 
check for proper ventilation.
Ambient temperature is too high; provide 
sufficient ventilation.
Low fluid level; add fluid.
Clogged fluid filter; change the fluid filter 
element as indicated by Supervisor™ control.
Thermal valve not functioning properly; replace 
element.
Open or shorted T1 or T2 sender; check for a 
short or open circuit to probe and correct 
wiring.
Low fluid pressure (LOW 
PRESSURE P3 DISPLAY)
Check fluid level.
Check for clogged fluid filter.
Cooling fan motor (FAN OL 
display)
Check the cooling fan motor.
Table 7-1: Troubleshooting Guide
SYMPTOM PROBABLE CAUSE REMEDY