24 SUNFAR E300 SERIES
F0.10 Parameter read-in protection Setting range:0 ~ 9999
It is used for avoiding any data wrong modification.
1:Only allow modifying parameter [F0.1] and this parameter
2:Only allow modifying this parameter
Other data::all parameter can be modified
When forbid modifying parameters, it will display “- -” if try to make any modification.
Some parameters can not modify when running. If try to modify, it
will display “ --”. If modify parameters, please make any
modification when inverter stops running.
F0.11 Torque boost Setting range:0.0 ~ 20.0(%)
It is used for improving inverter low freq torque characteristic. When runs under low freq, it will
boost compensation for inverter output volt shown as fig 6-5.
Boost volt = × [F0.13]
[F0.11]
100
Boost
volt
Freq [F0.12]
Volt
[F0.13]
[F0.11]
Fig 6-5 Torque boost diagram
E300 Series Mini-type Integrated Universal Inverter Manual