6 DESCRIPTION OF SPECIFIC FUNCTIONS
6.1 Basic operation parameter unit
F0.0 Freq input channel/mode selection Setting range:0 ~ 4
Select setting channel/mode of inverter running freq.
0: Digital set
Inverter setting freq is set by parameter [F0.1].
1: External input signal
Running freq is set by external input volt signal (0~10V) or current signal (0~20mA). Please refer
to parameter [F1.0] and [F1.1] for explanation of relative characteristics.
2: Serial communication terminal
By serial RS485 interface, receive freq setting order from PC or master.
3: Panel potentiometer
Running freq is set by panel potentiometer.
4: External terminal selection
By external multi-function terminals, confirm freq input channel (selection of function terminal is
set by parameter [F1.7]~[F1.9]).
Freq set selects terminal 2 Freq set selects terminal 1 Freq setting channel
0 0 Digital set
0 1 External input signal (0~10V/0~20mA)
1 0 RS485 interface
1 1 Panel potentiometer
Note: Terminal and CM closed is valid as 1.
F0.1 Freq digital set Setting range:0.0 Hz ~upper freq
When freq input channel selects digital set ([F0.0] = 0), inverter output freq is controlled by this
value. Under operation panel normal monitor mode, press key to modify this parameter
directly.
F0.2 Operation channel and mode selection Setting range:0000 ~ 1122
Select inverter operation order channel and the function of key .
1
st
of LED:Operation order channel selection
0:Keypad control
STOP
RUN