61
PPaarraammeetteerr
DDeessccrriippttiioonn
AI port
AI1~AI4 available
Q-Method
kW: set active power value
%: set active power percentage
Min. Lower limit: 0.0
Max.
When "Q-Method" is set to "%", the upper limit is 100.0%
When "Q-Method" is set to "kW", the upper limit is 999999
kW
Step
The minimum difference value between two consecutive
power dispatching instructions
Note: *Only when the control method is set to "Closed-loop control", the parameter "-
Select energy meter" is settable.
step 4 After finishing parameter setting, click "Save" to save the operation.
-- -- EEnndd
10.2.1.5 Digital Input
When using the digital signal at the DI port of the Logger3000 as the dispatching input,
set the active control mode to "Digital input".
step 1 Click "Power control" -> "Active power" to enter the active power interface.
step 2 Set the active control mode to "Digital input".
step 3 Set DI control parameters. For specific parameter description, refer to the following
table.
User Manual 10 Grid Dispatching