10.2.1.7 Scheduling Prohibited
Set the active control mode to "Scheduling prohibited" if the Logger3000 is prohibited to
perform active dispatching on the inverter.
step 1 Click "Power control" -> "Active power" to enter the active power interface.
step 2 Set the active control mode to "Scheduling prohibited" and click “Save”.
-- -- EEnndd
10.2.2 Reactive Power
10.2.2.1 Disable
If the grid company does not need the power plant to adjust the voltage at the grid-
connection point, and the inverter does not need to cooperate with the grid for reactive
power compensation, the inverter keeps operating in the reactive-forbidden output
state, and the Reactive control mode is set to "Disable".
step 1 Click "Power control" -> "Reactive power" to enter the reactive power interface.
step 2 Set the reactive control mode to "Disable" and click “Save”.
-- -- EEnndd
10.2.2.2 Remote Power Control
When the instruction source is IEC104 or MODBUS TCP protocol, set the "Reactive
control mode" to "Remote power control".
step 1 Click "Power control" -> "Reactive power" to enter the reactive power interface.
step 2 Set the "Reactive control mode" to "Remote power control".
step 3 Set remote dispatching parameters. For specific parameter description, refer to the
following table.