EasyManua.ls Logo

Sungrow SC1200UD - Page 64

Sungrow SC1200UD
137 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
56
step 5 Strip off the insulation cover of the cable end with a stripped length of 5mm longer than the
depth of the cable lug. It is advisable to use DT×××-12 (xxx is the cross-sectional area of the
cable selected) copper lug according to the cable specification.
step 6 Crimp the cable lug.
1 Put the stripped cables inside the cable lug.
2 Tighten the cable lug with proper tools at least twice.
step 7 Install the heat-shrinkable tubing.
1 A tubing with a length of 2cm longer than the cable lug is recommended;
2 Insert the heat-shrinkable tubing into the cable lug;
3 Shrink the tubing with hot air blower.
Cable protectors are advisable in the cable crosses if the multi-core cables are
used.
step 8 Connect cable L1 to the L1, i.e. phase A(U) in the transformer low-voltage side winding.
1 Select proper bolt to connect the cable lug to the copper bar (if it is the standard PCS,
the M12 bolt is within the scope of delivery).
2 Crimp the cable lug on the AC copper bar following the connection sequence shown in
the figure below.
3 Fasten the bolt with screwdriver or wrench with a torque of 89 N·m.
figure 6-12 Connection sequence
A B C D E F
Copper Bus Cable lug Bolt Disc spring
washer
Flat washer Nut
6 Electrical Connection User Manual

Table of Contents

Related product manuals