EasyManua.ls Logo

Sungrow SC1200UD - Page 65

Sungrow SC1200UD
137 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
57
The specification and number of AC cables should be selected properly according to on-site
situation. At most 6 cables can be connected. If more than 6 cables are used, please follow
the sequence below to connect them.
figure 6-13 Connection sequence when two cable lugs are used
A B C D E F
Copper Bus Cable lug Bolt Disc spring
washer
Flat washer Nut
• Incorrect AC connection sequence may cause fire. Please notice the cable con-
nection sequence.
• Ensure the fastness of the connection parts. Poor contact or oxidation of the
contact surface may cause fire.
• Long bolts may affect the insulation and may cause short circuit.
• Remove the heat-shrinkable tubing between the cable lug and the copper bar if
necessary. Poor contact or device damage may follow if otherwise.
step 9 Follow the same procedure in Step 6 to connect cable L2 to the L2, i.e. phase B(V) in the
transformer low-voltage side winding; connect cable L3 to the L3, i. e. phase C (W) in the
transformer low-voltage side winding; leave cable N unconnected.
Yellow, green, and red heat-shrinkable tubings are recommended respectively for
L1, L2, and L3 AC output cables to distinguish the phase.
step 10 Check to make sure the connection is secure.
User Manual 6 Electrical Connection

Table of Contents