THREE PHASE HI 25/50kW | Installer Manual14
Selecting the Mounting Area
For proper heat dissipation, allow a clearance of approximately 500mm to the side, 500mm above and below
the unit, and 1000mm to the front of the unit.
DO NOT install the inverter in the following areas:
Areas with high salt content, such as the marine environment. It will deteriorate the metal parts and
possibly lead to water/dampness penetrating the unit.
Areas lled with mineral oil or containing splashed oil or steam, such as those found in kitchens. It will
deteriorate plastic parts of the unit, causing those parts to fail or allowing water/damp to penetrate the
unit.
Areas that generate substances that adversely aect the equipment, such as sulphuric gas, chlorine gas,
acid, or alkali. These can cause the copper pipes and brazed joints to corrode and fail to conduct elec-
tricity reliably.
Areas that can cause combustible gas to leak, which contains suspended carbon-bre or ammable
dust, or volatile inammable such as paint thinner or gasoline.
Areas where there may be gas leaks and where gas may settle around the unit as this is a re risk.
Areas where animals may urinate on the unit or ammonia may be generated.
High altitude areas (over 4000 metres above sea level).
Environments where precipitation or humidity is above 95%
Areas where the air circulation is too low.
ALSO CONSIDER:
Installing the indoor unit, outdoor unit, power supply cable, transmission cable, and remote control cable
at least 1 metre away from any television or radio receiver. This will prevent TV reception interference or
radio noise. This will prevent radio signal interference from external units that might interfere with the
Wi-Fi or GSM monitoring.