THREE PHASE HI 25/50kW | Installer Manual66
To check the fault codes click on the FAULT CODES icon on the settings menu.
If any of the fault messages listed in the following table appear on your inverter and the fault has not been
removed after re-starting, please contact your local vendor or service centre. The following information is
required:
1. Inverter serial number.
2. Distributor or service centre of the inverter.
3. On-grid Power Generation Date.
4. The problem description (including the fault code and indicator status displayed on the LCD) with as much
detail as possible.
5. Owner’s contact information.
FAULT CODES
Error Code Description Solutions
F01 DC_Inversed_Failure
1. Check the PV input polarity.
2. Seek help from us, if can not go back to normal state.
F07 DC_START_Failure
1. The BUS voltage can't be built from PV or battery.
2. Restart the inverter, if the fault existis, please contact us.
F13 Working_Mode_Change
1. When the grid type and frequency changed it will report
F13;
2. When the battery mode was changed to "No Battery"
mode, it will report F13;
3. For some old FW version, it will report F13 when the sys-
tem work mode changed;
4. Generally, it will desappear automatically when shows F13;
5. If it remains same, turn on DC and AC switches for one
minute, then turn on the DC and AC switches;
6. Seek help from Sunsynk.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SunSynk SUNSYNK-25K-SG01HP3-EU-BM2 and is the answer not in the manual?

SunSynk SUNSYNK-25K-SG01HP3-EU-BM2 Specifications

General IconGeneral
BrandSunSynk
ModelSUNSYNK-25K-SG01HP3-EU-BM2
CategoryInverter
LanguageEnglish

Related product manuals