Page | 48
First of all, leave the main supplies off. Next, connect all communication cables, set up all
LCDs and then, last of all, turn on the main supplies.
Q2: What are the indications that the communication and the system are ok or not?
Parallel errors will be shown as fault F46 on the display.
Q3: What are the consequences of not setting one inverter in a parallel mode?
It can damage the inverter.
Q4: What are the consequences of having more than one Master Inverter or having
no inverter set as ‘Master’?
It can damage the inverter. There are cases in which it is possible to have more than one
master. For example, as aforementioned, six inverters paralleled in a three phase utility
grid (three masters).
Q5: What are the consequences for setting A, B, or C phases wrong while in parallel
mode?
It can damage the inverter. Recommend checking the phase rotation with a meter before
switching on.
Q6: What are the consequences of factory resetting, power cycling, or firmware
updating one inverter in a parallel system?
There is no consequence, but the master inverter will keep controlling the slaves.
Q7: What consequences for changing ALL/ANY settings while operating in parallel
mode?
It can damage the inverter and fault F46 will be indicated on the display.
5.17. Solar Power Generated
This page shows the daily, monthly, yearly, and total solar power produced. Access this page by
clicking on the ‘Solar/Turbine’ icon on the Home Page.