Supmeter BST106-B60S(L) - System Calibration Procedures (F2-CAL); System Calibration Overview

Supmeter BST106-B60S(L)
39 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
25
6.3.2 Data Calibration (dAtA)
6.3.2.1mVData Calibration
Input the specification parameter values of loadcell according to the actual configuration of the weighing
system to correct Span Coefficient. If there is no access to get the specification parameter values for Data
Calibration, then its necessary to do Load Calibration.
Note:
Total Capacity of Loadcells = Loadcell Capacity × Loadcell Number.
Voltage Ratio = Excitation Voltage on the terminal of controller / Excitation Voltage on the terminal of
loadcells.
The rated excitation voltage for loadcells is DC5V. It’s best to measure the actual voltage value.
Main Display Interface
+】【
+】【
Input Total Capacity of Loadcells:
1~99999 Weight Unit.
: Exit : Save
M
Input Output Sensitivity of Loadcell
[E]: 0.500~5.000mV/V.
Input Voltage Ratio’ [V]:
1.000~2.000.
[105] Span Coefficient value.
M
Prompt Message:
[19.5EV]:mVData Calibration.